RCCB

Residual Current Circuit Breaker

Home>AC Switch>RCCB

Features

Function: Leakage current protection, ensuring people’s safety against electrocution and fire. (For people protection)
Type: AC, A, B
Standard: IEC 61008-1

RCCB Type Symbols Feature
AC Alternating Current only
A Full type AC features,
+ Detection of pulsating current with DC components
B

Full type A features,
+Detection of high frequency currents up to 1kHz,
+ smooth DC currents.

Main Ratings According to IEC 61008-1

Type AC A B
Model Electromagnetic Electromagnetic Electromagnetic
Poles 1P+N, 3P+N 1P+N, 3P+N 1P+N, 3P+N
Rated Voltage (Un) 240V/415V 240V/415V 240V/415V
Insulation Voltage (Ui) 500V 500V 500V
Rated Impulse Withstand Voltage (Uimp) 4kV 4kV 4kV
Rated Frequency 50/60Hz 50/60Hz 50/60Hz
Rated Current (In) 16A, 20A, 25A, 32A, 40A, 50A, 63A 16A, 20A, 25A, 32A, 40A, 50A, 63A 16A, 20A, 25A, 32A, 40A, 50A, 63A
Rated Residual Operated Current (I△n) 30mA, 100mA, 300mA 30mA, 100mA, 300mA 30mA, 100mA, 300mA
Rated Residual Non-operated Current (I△no) 0.5 0.5 0.5
Rated Limited Short-circuit Current (Icn) 6kA 6kA 10kA
Rated Limited Residual Short-circuit Current (I△c) 6kA 6kA 10kA
Rated Making and Breaking Capacity (Im) 500A(In≤50A), 630A(In=63A) 500A(In≤50A), 630A(In=63A) 1kA
Rated Residual Making and Breaking Capacity (I△m) 500A(In≤50A), 630A(In=63A) 500A(In≤50A), 630A(In=63A) 1kA
Electrical Life ≥2,000 ≥2,000 ≥2,000
Mechanical Life ≥4,000 ≥4,000 ≥4,000
Operating Temperature -25℃~ 40℃ -25℃~ 40℃ -25℃~ 40℃
Storage Temperature -25℃~ 70℃ -25℃~ 70℃ -25℃~ 70℃
Degree of Protection IP20 IP20 IP20
Basic Dimension 36(72)x82x71 36(72)x82x71 54(72)x82x77
Mounting 35mm DIN Rail 35mm DIN Rail 35mm DIN Rail